Eslami Nejad, ParhamBadache, MessaoudOuzzane, MohamedAidoun, ZineIGSHPA Technical/Research Conference and Expo (2017)2017-03-062017-03-062017http://hdl.handle.net/20.500.14446/49332In an attempt to address recent challenges on using natural refrigerants and to develop further knowledge and expertise in the field of direct expansion ground source heat pump (DX-GSHP), an experimental transcritical carbon dioxide (CO2) test bench was built at CanmetENERGY Research Laboratory. A previously developed theoretical model of the system was modified and validated against a set of experimental results and adopted to investigate the system performance in a wide operating range. A parametric analysis was also performed using the theoretical model for understanding the system and at exploring the performance improvement actions for future installations. Validation results showed that the model predicts the experimentation very well within the uncertainty of the measurement. Furthermore, parametric analysis showed that improper control of some parameters such as gas cooler CO2 outlet temperature and discharge compressor pressure can degrade the system performance by up to 25% and the heat pump heating capacity by 7.5%.application/pdfIn the Oklahoma State University Library's institutional repository this paper is made available through the open access principles and the terms of agreement/consent between the author(s) and the publisher. The permission policy on the use, reproduction or distribution of the article falls under fair use for educational, scholarship, and research purposes. Contact Digital Resources and Discovery Services at lib-dls@okstate.edu or 405-744-9161 for further information.ground source heat pump systemsrefrigerantsDirect expansion ground source heat pump using carbon dioxide as refrigerant: Test facility and theoretical model presentation10.22488/okstate.17.000526Conference proceedings